AC or Solar Charged The most common reason for this type of problem is a bad battery. It is highly recommended that the battery be load tested at a battery store to verify that it is good. The load test is the only sure way to know if we have a good ...
This problem is probably due to a bad receiver. First locate the “LED Indicator” push button on the Ranger control board. Then locate the “Push Button Input” LED located below the J2 terminal plug of the Ranger control board. Press the “LED ...
The first thing to check is the accessory wiring. The accessory needs power (+12 vdc) wired to J2 terminal 5 on the Ranger control board. It also needs ground, which can be wired to the battery or to J2 terminal 2 or 7 on the Ranger control board. ...
LCR Receiver Only The problem is most likely the programming of the LCR receiver (P2 relay is programmed to latch mode) On the Ranger control board locate press and hold the “LED Indicator” pushbutton. Look below the J2 terminal plug of the Ranger ...
LCR Radio Equipment Only Open the control box and locate the Ranger control board. Locate the “LED Indicator” push button and the “Push Button Input” LED under J2 Terminal 3. Push and hold the “LED indicator” push button, then press the transmitter ...
Dual Gate opens or closes correctly then immediately reverses direction. Locate the SW1 switches on the Ranger control board. Switch 3 and 4 should be turned on for a dual gate, turn off switch 4. This will disable one gate. Operate the gate and ...
Open the control box cover and locate the Ranger control board. Locate the sensitivity adjustment potentiometer located on the control board. The white center is adjustable and needs to be turned in a clockwise direction to increase force. Normally a ...
If SW1 switch 1 is on then the gate should automatically close from any position. Locate the “Open/Close Command “ push button. Press the button to verify that the gate will close. If gate closes correctly then proceed to the steps below. Verify that ...
Monitored Entrapment Devices Are Installed Contact Edge with 10K Resistor Monitoring Verify that dip switch SW1 switch 10 (contact edge monitor) is ON pressed down on the right hand side. Press and hold the LED indicator on the control board. Verify ...
Follow steps 1 through 7 above. Disconnect the actuator connectors plugged into the control board Gate 1 and Gate 2 (X1 and X2). Then locate the SW1 dipswitches on the control board. Turn off switch 4 (down on left side) and turn on switch 3 (down on ...
Open the control box cover locate the “Open/Close Command” push button and press it to operate the gate. Press the “Reset” push button located above the “Open/Close Command” button, then push the “Open/Close command” push button to operate the gate. ...
!!! IMPORTANT FIRST STEP !!! First thing to verify is that no monitored entrapment devices are creating the problem. Press the Open/Close button on the control board. If gate does not operate proceed to step 2. Press the Type D S4 push button and ...