Ranger HD - Single or Dual Gate Will Not Operate
Monitored Entrapment Devices Are Installed
- Verify that dip switch SW1 switch 10 (contact edge monitor) is ON pressed down on the right hand side.
- Press and hold the LED indicator on the control board.
- Verify the LD3 LED (Contact edge 2nd entrapment) located below the J2 plug is OFF.
- If ON then check wire connections from contact edge for proper connection.
- If wires are good then verify the contact edge has a 8.25k or 10k resistor installed. Verify by disconnecting and checking with meter.
- Activate the contact edge by depressing it and verify the LD3 LED is ON bright.
- If not, contact edge is bad.
- Verify that SW1 dip switch 10 is ON press down on the right hand side.
- Verify that dip switch SW1 switch 7 or 8 (photo eye monitor) is ON press down on the right hand side. Turn ON the ones being used.
- Turn dip switch SW1 3 and 4 OFF. Allows power to be applied to photo eye.
- Press and hold the LED indicator button located on the control board.
- Verify that LD4 or LD5 LED (Photo eye N/C) located below J2 on the control board is ON.
- If not verify alignment between photo eye transmitter and receiver. Correct if necessary.
- If not then check wire connection from photo eye for proper connection.
- If LD4 or LD5 are ON verify that the Led goes OFF when photo eye beam is broken.
- If LED does not turn OFF when beam is broken then photo eye is bad.